Apollo XP95 Visual Alarm Devices

Product Code: F/55

Addressable EN54 Various EEA
System  Approval Weight  Conformity

A European standard has been published to assess the performance of VADs, which were often referred to as ‘beacons’ or ‘sounder beacons’. They assist hearing impaired people or staff working in noisy environments to recognise when a fire alarm has been activated. EN54-23:2010 has been introduced to standardise the requirements, and performance of VADs to ensure that adequate light intensity is achieved where required.

Email this product to a friend
Like on Facebook
Share this product on Twitter
  • Ceiling Mounted: When mounted on a ceiling a level of 0.4 lux is archived over a known area
  • Wall Mounted: When mounted on a wall a level of 0.4lux is archived over a known area
  • Open Category: Manufacturers specify the area coverage of the VAD.
  • F/55000-742 | Ceiling Mounted Red Body White Flasg 9.4mA in alarm 8.5m coverage @3m mounting height
  • F/55000-745 | Ceiling Mounted White Body White Flash 9.4mA in alarm 8.5m coverage @ 3m mounting height
  • F/55000-740 | Ceiling Mounted Red Body White Flash 26.6mA in alarm 15m coverage @ 3m mounting height
  • F/55000-743 | Ceiling Mounted White Body White Flash 26.6mA in alarm 15m coverage @ 3m mounting height
  • F/55000-741 | Wall Mounted Red Body White Flash 9.4mA in alarm 7m³ coverage @ 2.5m mounting height
  • F/55000-741 | Wall Mounted White Body Red Flash 9.4mA in alarm 7m³ coverage @ 2.5m mounting height
  • F/45681-709 | Open Category Base mounted VAD white flash 9.4mA in alarm Approx coverage 3m Dia @3m mounting height
  • F/45681-705 | Ceiling mounted Base mounted Sounder/VAD white flash 14mA in alarm Approx coverage 3m Dia @3m mounting height