FIRE DETECTION SYSTEMS | AUTOMATIC OPENINGVENT SYSTEM | 75 t: 0845 884 7000 | f: 0845 884 6000 | w: www.channelsafety.co.uk | @channelsafety | EDITION 7 AOV Smoke Ventilation System SYSTEM LAYOUT & WIRING The diagram below shows the typical system architecture for a single zone panel system. Link 1 & 2 Trigger inputs for AOV panel. Closed circuit loop when broken will cause the panel to trigger vents, windows or domes. Ov k/s Trigger input for a Fireman’s override call point. This can be either keyswitch or rocker switch. ACT 24v DC output for actuators, vents or domes. Opening (forward) = 24v DC + Closing (reverse) = 24v DC - Normal state = no voltage AOV SINGLE ZONE CONTROL PANEL F/CH/AOV-003 AOV single zone base unit 2.5 amp 24v F/CH/AOV-005 AOV single zone base unit 4 amp 24v F/CH/AOV-007 AOV single zone base unit 10 amp 24v AOV MULTI ZONE CONTROL PANEL F/CH/AOV5/A AOV multi zone (1-5 zones) base unit 5 amp 24v (Requires 1x F/CH/AOVZ-01 for each zone) F/CH/AOV10/A AOV multi zone (1-5 zones) base unit 10 amp 24v (Requires 1x F/CH/AOVZ-01 for each zone) F/CH/AOV10/B AOV multi zone (6-10 zones) base unit 10 amp 24v (Requires 1x F/CH/AOVZ-01 for each zone) F/CH/AOV20/B AOV multi zone (6-10 zones) base unit 20 amp 24v (Requires 1x F/CH/AOVZ-01 for each zone) F/CH/AOVZ-01 AOV Zone card for multi zone control panels. (1x F/CH/AOVZ-01 is required for each working zone) (OUTPUT OPTIONS) AOV ACTUATORS F/CH/ACT-301 24v DC 1.35 amp actuator - 300N - reach 100mm to 400mm adjustable (L-290 x W-83 x H-48mm) Requires bracket for fixing (see below) F/CH/ACT-501 24v DC 2 amp actuator - 400N - reach 800mm fixed (L-575 x W-80 x H-50mm) Requires bracket for fixing (see below) F/CH/ACT-502 24v DC 2 amp actuator - 400N - reach 600mm fixed (L-650 x W-80 x H-50mm) Requires bracket for fixing (see below) F/CH/ACT-503 24v DC 2 amp actuator - 400N - reach 450mm fixed (L-765 x W-80 x H-50mm) Requires bracket for fixing (see below) F/CH/ACT-701 24v DC 1 amp actuator - 200N - reach 380mm fixed (L-473 x W-51 x H-40mm) F/CH/ACT-702 24v DC 1 amp actuator - 200N - reach 600mm fixed (L-613 x W-51 x H-40mm) F/CH/ACT-703 24v DC 1 amp actuator - 200N - reach 800mm fixed (L-713 x W-51 x H-40mm) BRACKETS FOR AOV ACTUATORS F/CH/BRK-301 Standard mounting bracket suitable for use with F/CH/ACT-301 F/CH/BRK-303 Small swivel mounting bracket suitable for use with F/CH/ACT-301 F/CH/BRK-304 Large swivel mounting bracket suitable for use with F/CH/ACT-301 F/CH/BRK-502 Standard swivel mounting bracket suitable for use with F/CH/ACT-501, F/CH/ACT-502 or F/CH/ACT-503 (INPUT OPTIONS) AOV CALL POINTS & DETECTORS F/CH/FVE/BGU Smoke vent yellow break glass unit (no resistor) F/CHBG/S/KS Smoke vent yellow keyswitch (2 positions) open - closed F/CHBG/KS/SV Smoke vent yellow keyswitch (3 positions) automatic - open - closed F/CHSW/2/Y Smoke vent yellow rocker switch (2 positions) open - closed F/CHSW/3/Y Smoke vent yellow rocker switch (3 positions) automatic - open - closed BATTERIES B/12V/7AH/SLA 12 Volt 7Ah sealed lead acid battery (1 block) - Suitable for 1-5 amp PSUs B/12V/12AH/SLA 12 Volt 12Ah sealed lead acid battery (1 block) - Suitable for 10 amp PSUs F/CH/FVE/BGU F/CHSW/2/Y or F/CHSW/3/Y F/CH/CHBG/S/KS or F/CH/CHBG/KS/SV