24 | EMERGENCY LUMINAIRES | EMERGENCY LIGHTING BATTERIES t: 0845 884 7000 | f: 0845 884 6000 | w: www.channelsafety.co.uk | @channelsafety | EDITION 7 NiCd Batteries PRODUCT FEATURES • Available exclusively from channel safety systems • High quality 4.0Ah nickel cadmium batteries • Complete with connector and lead • 1.2V per cell • 55°C high temperature • Dimensions: Each cell 33mmØ x 60mmL (approx) • Weight: 0.125 Kg per cell • Compliance: IEC 61951 - 2003 Clause 7.4.2.3 • Endurance test - 3rd party certified BATTERY CONFIGURATIONS PRODUCT CODE DESCRIPTION A B/1.2V/4AH/NICD NiCd 4.0Ah High Temperature D Cell Tags B B/2.4V/4AH/NICD NiCd 2 Cell 4.0Ah High Temperature D Cell Leads C B/2.4V/4AH/NICD/S NiCd 2 Cell 4.0Ah High Temperature D Cell Leads Side-By-Side D B/3.6V/4AH/NICD NiCd 3 Cell 4.0Ah High Temperature D Cell Leads E B/3.6V/4AH/NICD/S NiCd 3 Cell 4.0Ah High Temperature D Cell Leads Side-By-Side F B/4.8V/4AH/NICD NiCd 4 Cell 4.0Ah High Temperature D Cell Leads G B/4.8V/4AH/NICD/S NiCd 4 Cell 4.0Ah High Temperature D Cell Leads Side-By-Side H B/6V/4AH/NICD NiCd 5 Cell 4.0Ah High Temperature D Cell Leads I B/6V/4AH/NICD/S NiCd 5 Cell 4.0Ah High Temperature D Cell Lead Side-By- side Electrical characteristics per cell Nominal Voltage (V) 1.20 Nominal Capacity (mAh) @ 25˚C 4000 Maximum Continuous Discharge Current (A) 2.4 Dimensions per cell Diameter (mm) 32.5 +/- 0.5 Height (mm) 59 +/- 1.0 Weight (g) 125 approx. Charge conditions Time Temp Charge (mA) Standard 16hrs 0-45˚C 400mA (0.1C) Trickle 24hrs 0-70˚C 200mA (0.05C) Maintenance ∞ 0-55˚C 200mA (0.05C) Storage Storage Temperature 0 to +25˚C A B C D E F G H I BATTERY CONFIGURATIONS