- Lighting
- Fire
- Conventional Fire Alarm
- Conventional 2 Wire Fire Alarm
- Analogue Adressable Systems
- Apollo series 65 Conventional Fire Detectors
- Call Points & Power Supplies
- Electronic Sounders and Bells
- Radio Fire Alarm Systems
- Specialist Detection Devices
- Fire Accessories
- Voice Alarm / Public Address Systems
- Detector & Battery Test Equipment
- Monitoring Systems
- DDA
- Medical
- Knowledge
Firewatch 1001

The Firewatch 1001 is an economical, flexible yet highly sophisticated analogue addressable fire alarm control panel.
Available in three variants - one loop 16 zone, one loop 32 zone and two loop 32 zone - its key strengths are its low cost and its ability to be networked with up to 8 master panels (any mix) per network and 4 repeater panels per master.
SPECIFICATION
- Compatible with XP95, Discovery and Xplorer protocols
- Designed to comply with EN54 parts 2 & 4
- Two independently programmable conventional sounder circuits
- Two programmable inputs
- A fault output relay and three programmable relay outputs with volt free changeover contacts
- A selection of zone dependency functions (type A, B or C) as detailed below:-
- Type A - If there is an alarm from a detector, the panel will look for a confirmatory alarm from the same or another detector in the same zone before a full alarm is established. If there is no confirmatory alarm, the first alarm will automatically reset
- Type B - As type A except the confirmatory signal must be from another detector in the same zone
- Type C - As type A except the confirmatory signal may also be from another zone, and the first alarm will not automatically reset
- A day/night (building occupied/unoccupied) function (engineer programmable changes include detector sensitivity (high/low) and zone dependency settings
- An investigation delay period function (programmable for length of time, which zone(s) it applies to and whether or not it operates in day/night mode)
- Individual sensitivity settings for each device
- A phased evacuation facility
- An alarm counter to record the number of times the panel has been in alarm
- Powerful short circuit protected loop drivers, capable of supporting up to 40 loop powered 10mA sounders per loop
- An integral EN54-4 switch mode PSU rated @ 185-260V a.c. 50/60Hz (1.4A on 16 zone panel, 3A on 32 zone panel)
- Adjustable contamination levels
- Earth fault monitoring
- Push button access code or keyswitch entry to access levels 2 and 3 (dependent on the model purchased)
- 40 characters of custom text per device
- 500 event monitoring
- Comprehensive test, maintenance and commissioning functions
- An intuitive Windows based uploaddownload PC program (part no. FW1001/SOFTWARE) for system configuration
| Sophisticated sounder group mapping (left) and complex cause and effect scenarios (below) can be easily implemented using the Firewatch 1001’s intuitive upload-download PC programming software. | |
FW1001 CONTROL PANELS | |
| CODE | DESCRIPTION |
| FW1001/1/16 | Networkable single loop 16 zone panel, code entry, c/w 1.4A psu, plastic lid/back box |
| FW1001/1/16/K | Networkable single loop 16 zone panel, keyswitch entry, c/w 1.4A psu, plastic lid/back box |
| FW1001/1/32 | Networkable one loop 32 zone panel, code entry, c/w 3A psu, metal lid, metal back box |
| FW1001/1/32/K | Networkable one loop 32 zone panel, keyswitch entry, c/w 3A psu, metal lid, metal back box |
| FW1001/2/32 | Networkable two loop 32 zone panel, code entry, c/w 3A psu, metal lid, metal back box |
| FW1001/2/32/K | Networkable two loop 32 zone panel, keyswitch entry, c/w 3A psu, metal lid, metal back box |
FW1001 ANCILLARIES | |
| FW1001/NCC/16 | Network communications card for 16 zone panels - one required per master panel |
| FW1001/NCC/32 | Network communications card for 32 zone panels - one required per master panel |
| FW1001/Bez | Flush mounting bezel (for 32 zone masters & repeaters) |
| FW1001/P | Printer kit, including printer, lead and socket |
| FW1001/Software | FW1001 PC programming upload download software, Windows |
Click here for detailed product info Click here for installation guide | |